Yokogawa EJA110-EMS4B-92DB

Yokogawa EJA110-EMS4B-92DB DIFFERENTIAL PRESSURE TRANSMITTER
EJA110A general introduction:

The high performance differential pressure transmitter model EJA110A can be used to measure liquid, gas, or steam flow as well as liquid level, density and pressure. It outputs a 4 to 20 mA DC signal corresponding to the measured differential pressure. Model EJA110A also features remote setup and monitoring through communications with the BRAIN™ terminal and CENTUM CS™ or XL™ or HART® 275 host.

Commonly used EJA110A:
EJA110-ELS4B-32DD/KS2-E1 EJA110A-EMS5B-97EN/FU1/N4 EJA110A-EMS4B-9CDB/FU1/D4
EJA110-EHS4B-32DD/KS2-E1 EJA110A-EMS5B-97DB/FU1/X1/A/D1 EJA110A-ELS4A-97ED/FF1/D1/C1/N4/M11 EJA110A-ELS4A-92DB EJA110A-EMS4A-92DB
EJA110A-EHS5B-97DB/FU1/X1/A/D1/M01/T12 EJA110A-EMS5B-97EN/FU1/N4 EJA110A-EHS4B-7CDK/FF1/D1/M11/T12 EJA110A-EHS4B-3CDK/FF1/D1/M11/T12

EJA110A Technical Datas:

EJA110A Differential Pressure Transmitter
L CapsuleM CapsuleH CapsuleV Capsule
Range-10 to 10 kPa-100 to 100 kPa-500 to 500 kPa-0.5 to 14 MPa
(-40 to 40 inH2O)(-400 to 400 inH2O)(-2000 to 2000 inH2O)(-70 to 2000 psi)
Span0.5 to 10 kPa1 to 100 kPa5 to 500 kPa0.14 to 14 MPa
(2 to 40 inH2O)(4 to 400 inH2O)(20 to 2000 inH2O)(20 to 2000 psi)
Accuracy±0.075%±0.065%±0.065%±0.065%
Degrees of protectionIP67, NEMA 4X, and JIS C0920 immersion proof
CertificatesFM, CENELEC ATEX, CSA, IECEx
Output4 to 20 mA DC, FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication
Supply voltageBRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model)
Ambient temperature-40 to 85 deg C (-40 to 185 deg F) (general use type)
-30 to 80 deg C (-22 to 176 deg F) (with integral indicator)
Process temperature-40 to 120 deg C (-40 to 248 deg F) (general use type)
Maximum working pressure16MPa(2300psi)
3.5MPa(500psi) for L capsule with special materials
Mounting2-inch pipe mounting
Wetted parts materialCapsuleSUS316L(Diaphragm material is Hastelloy C-276),
Hastelloy C-276, Tantalum, Monel
Cover flangeSUS316, Hastelloy C-276, Monel
HousingCast aluminum alloy or SUS316 equivalent stainless steel (optional)
Posted in InventoryList.